Designed for strict control of room pressurization to create continuous directional airflow from the outside of the lab to the Class II bio-safety cabinets in the lab. |
 |
Provided supply and exhaust air tracking through the DDC system to maintain the critical negative pressurization in the lab space for biological hazard containment to BSL-3 standards. |
 |
Designed with interior surfaces for easy cleaning and decontamination, and sterilization for all materials exiting the lab. |
 |
Designed MEP utilities for a new autoclave and four bio-safety cabinets, and critical temperature monitoring for new lab freezers. |
 |
Removed or capped any utility that could circumvent the BSL-3 envelope such as vacuum and drain lines. |
 |
Designed new 480V and 120/208V normal, emergency and UPS power feeders and branches for new lab equipment. |